Details
RM Series 60-600kVA Modular Online UPS (380V/400V/415V)
The RM Series 60-600kVA Modular Online UPS features an innovative new topology with a bidirectional DC-DC converter circuit, significantly enhancing system performance and ensuring high efficiency. Its compact design delivers exceptional power density, with the 600kW system occupying just 0.9m² of space. The RM Series offers an ideal power supply solution for large data centers and critical facilities.
Key Features
-
High Efficiency: Up to 97%
-
Lithium Battery Support
-
Intelligent Staggered Power Consumption: Enhanced flexibility and energy savings
-
Double-Sided DC-DC Topology: Supports charging power up to 30%
-
High Power Density
-
Battery Neutral-Free Design: Supports various battery configurations and horizontal DC voltages
-
User-Friendly Interface: 10" touch color LCD with graphic display for intuitive operation
-
Modular Design: Supports up to 30 power modules in parallel, hot-swappable with N+X redundancy
Bypass Monitoring Module
The RM Series includes a bypass and monitoring module equipped with intelligent slots, communication interfaces, battery cold start buttons, and ample dry contacts. These features ensure convenient data transfer and comprehensive system monitoring:
-
Multiple communication interfaces including RS485, USB, CAN, and programmable dry contacts
-
Convenient SD card slot for easy software updates and version upgrades in maintenance mode
-
Isolation between the LCD and monitoring board connected via network cable to improve reliability and protect DSP components
Power Module
The RM600/60D cabinet houses 10 power modules, each delivering 60kVA in a compact 2U height. With front panel knobs, these modules support hot-swapping without power interruption, enabling online redundancy and maintenance:
-
Compact modular cabinet design with up to 10 slots
-
Module status LEDs for real-time power module condition monitoring
-
Bidirectional DC-DC converter supporting 30% charging power, enhancing system performance
-
Overall efficiency up to 97%, with optimized battery and power grid collaboration for maximum UPS utilization
Specifications
Model | RM600/60D | |||||
System Capacity | 600kVA | |||||
Power Module Capacity | 60kVA/kW | |||||
Input | Dual Input | Standard | ||||
Phase | 3Phase+Neutral+Ground, 380/400/415VAC (line-line) | |||||
Rate Frequency | 50/60Hz | |||||
Input Voltage Range | 323~478Vac (line-line),full load 323V~138Vac (line-line), load decrease linearly from 100% to 40% according to the min phase voltage |
|||||
Input Frequency Range | 40Hz~70Hz | |||||
Inpput PF | >0.99 | |||||
Input THDi | <3% (100% Linear load) | |||||
Bypass | Rate Voltage | 380/400/415VAC (line-line) | ||||
Rate Frequency | 50/60Hz | |||||
Input Voltage Range | Settable, default -20%~+15% Up limit: +10%, +15%, +20%, +25% Down limit: -10%, -15%, -20%, -30%, -40% |
|||||
Bypass Frequency Range | Settable, ±1Hz, ±3Hz, ±5Hz | |||||
Bypass Overload | 110% for long term operation; 110%~125% for 5 mins; 125%~150% for 1 min; 150%~400% for 1 s; >400% less than 200ms |
|||||
Output | Rate Voltage | 380/400/415VAC (line-line) | ||||
Rate Frequency | 50/60Hz | |||||
Output PF | 1 | |||||
Voltage Regulation | ±1% | |||||
Output THDu | <1% Linear load; <5%, Non-linear load | |||||
Inverter Overload | <110%, 1hour; 110%~125%, 10mins; 125%~150%, 1min; >150%, 200ms |
|||||
Rate Frequency | 50/60Hz | |||||
Frequency Precision | ± 0.1% | |||||
Battery | Voltage | ±180~288VDC 30~32pcs derate to 0.7; 34~36pcs derate to 0.8; 38pcs derate to 0.9; 40~48pcs |
||||
Voltage Precision | 0.01 | |||||
Charge Power | Up to 30% * Output active power | |||||
System | Efficiency | AC Mode | >97% | |||
Battery Mode | >96% | |||||
Display | LED+Color touch LCD | |||||
Interface | Standard: RS485, USB, CAN, Programmable Dry Contact | |||||
Option | SNMP card, AS400 card, Parallel kit, SPD, Dual input kit, LBS, Common battery kit | |||||
Temperature | Operation: 0~40 ℃ Storage: -40~70 ℃ | |||||
Relative Humidity | 0~95% Non-condensing | |||||
Noise(1 meter) | 75dB @ 100% load, 70dB @ 45% load | |||||
Altitude | <1000m. Within 1000m~2000m, 1% power derating for every 100m | |||||
Application Standard | Safety: IEC/EN 62040-1 EMC: IEC/EN 62040-2 Performance: IEC/EN 62040-3 | |||||
Physical | Dimension (W*D*H,mm) | Cabinet | 800*1100*2000 | |||
Power Module | 550*750*85 | |||||
Weight (kg) | Cabinet | 443 | ||||
Power Module | 35.7 |