Details
HR11 Series Rack Online UPS
1-10kVA (220V/230V/240V)
The HR11 Series 1:1 Rack Online UPS is the perfect power protection solution for small data centers. This series supports built-in battery options, and the 6kVA and 10kVA models utilize advanced 3-level technology, ensuring compatibility with complex load conditions. Available models include 1kVA, 2kVA, 3kVA, 6kVA, and 10kVA.
Key Features (1-10kVA)
-
Wide input voltage range with input power factor >99%
-
Compatible with standard 19” racks and matching battery cabinets
-
Comprehensive protection against overvoltage, short circuits, and overheating
-
LCD/LED display for real-time system monitoring
-
Smart fan control with automatic speed adjustment
-
Versatile communication interfaces: RS232, USB, SNMP, Intelligent Card
Exclusive Features (6-10kVA Models)
-
High efficiency operation – up to 95%
-
True power output: kVA = kW, with power factor of 1
-
Smart charging management to enhance battery lifespan
-
Advanced 3-level inverter technology for superior load compatibility
Specifications
HR1101S | HR1101L | HR1102S | HR1102L | HR1103S | HR1103L | |
INPUT | ||||||
Cold Start | YES, default frequency=50Hz or settable | |||||
Acceptable Input Voltage | 110VAC~288VAC | |||||
100% load@>176VAC | ||||||
80% load@>154VAC | ||||||
70% load@>132VAC | ||||||
50% load@>110VAC | ||||||
Phase | Single phase in,single phase out | |||||
Transfer Voltage Range | (200VAC/208VAC/220VAC/230VAC/240VAC) | |||||
-Line low transfer | 110VAC | |||||
-Line low recovery | 121VAC | |||||
-Line high transfer | 288VAC | |||||
-Line high recovery | 281VAC | |||||
Input Current | ||||||
-Rating(nominal input voltage) | 4.8A | 9.6A | 14.4A | |||
Input Power Factor | ≥0.97 | |||||
Input Connection | IEC C14 | IEC C20 | IEC C20 | |||
Input Frequency Range | 40~70Hz | |||||
OUTPUT | ||||||
Frequency adaptable | Settable | |||||
Power | ||||||
-Power(kVA) max | 1 | 2 | 3 | |||
-Power(kW) max | 0.9(0.8 for 200VAC/208VAC) | 1.8(1.6 for 200VAC/208VAC) | 2.7(2.4 for 200VAC/208VAC) | |||
Output Voltage | ||||||
-Waveform(Bat. Mode) | Pure Sine Wave | |||||
-Nominal voltage | 200/208/220/230/240VAC | |||||
-Voltage regulation | ± 1 % | |||||
-Transient response | ≤5% (0% - 100% -0%) | |||||
-Transient recovery | ≤30ms (0% - 100% -0%) | |||||
-Voltage distortion | ≤2% THD, linear load | |||||
≤ 5.5% THD, non-linear load | ≤ 5% THD, non-linear load | ≤ 5% THD, non-linear load | ||||
Output Frequency | ||||||
-Synchronization range | ±5Hz default | |||||
-Battery mode | (50±0.1) Hz default | |||||
Transfer Time | ||||||
-Line mode to battery mode | 0 | |||||
-Inverter to bypass | 2ms | |||||
Efficiency | ||||||
-Line mode with battery full charged | 89%@100% load, 87%@50% load | 91%@100% load, 88%@50% load | 90%@100% load, 90%@50% load | |||
-ECO mode | 94.0% | 97.0% | 97.0% | |||
-Battery mode | 83%@100% load, 84%@50% load | 87%@100% load, 88%@50% load | 87%@100% load, 89%@50% load | |||
Noise(1m away) | <45dB@<60%load,<50dB@>60%load | <50dB@<60%load,<55dB@>60%load | <50dB@<60%load,<55dB@>60%load | |||
Overload Capability(Inverter) | 105%~130%: Transfer to bypass after 1 mins. | |||||
150%: Transfer to bypass after 30s | ||||||
Overload Capability(Battery Mode) | 105%~130%:shutdown after 10s | |||||
150%:shutdown after 5s | ||||||
Overload Capability (Bypass Mode) | <130%: Long time | |||||
>130%&<150%:Shutdown after 10min | ||||||
>150%&<180%:Shutdown after 5 seconds | ||||||
Output Connection | (6) IEC C13 | (6) IEC C13 | (6)IEC C13+(1)IEC C19 | |||
Crest Ratio | 3:1 | |||||
BATTERY | ||||||
Rating/Type | 12VDC/7Ah | Depend on the capacity of external batteries | 12VDC/7Ah | Depend on the capacity of external batteries | 12VDC/7Ah | Depend on the capacity of external batteries |
Quantity | 3 | 6 | 8 | |||
DC Voltage | 36VDC | 72VDC | 96VDC | |||
Back-up Time | 6mins @80% load | Depend on the capacity of external batteries | 6mins @80% load | Depend on the capacity of external batteries | 5.5mins @80% load | Depend on the capacity of external batteries |
Battery-Low Voltage | 33VAC~35VDC depending on load | 66VDC~70VDC depending on load | 88VDC~94VDC depending on load | |||
Backery Maintenance | Front Maintenance Online | |||||
Charger | ||||||
-Charging voltage | float:40.5VDC/boost:41.4VDC | float:81VDC/boost:82.8VDC | float:108VDC/boost:110.4VDC | |||
-Charging current (max) | 1A | 8A or 4A | 1A | 8A or 4A | 1A | 8A or 4A |
-Charging time | 8h recharge to 90% | Depend on the capacity of external batteries | 8h recharge to 90% | Depend on the capacity of external batteries | 8h recharge to 90% | Depend on the capacity of external batteries |
Leakage current | <1mA | <1mA | <1mA | |||
INDICATOR & ALARM | ||||||
-Display | LED+LCD | |||||
-Battery discharge | Sounding every 2 minutes | |||||
-Low battery | Sounding every 6 seconds | |||||
-Overload | Continuous beeping | |||||
-Fault | Continuous beeping | |||||
-Input voltage abnormal | Sounding every 2 minutes | |||||
-Warn | Sounding every 6 seconds | |||||
INTERFACE | ||||||
-Smart RS232 | Standard Cable support INVT Power Monitor Software | |||||
-SNMP(option) | Power Managment from SNMP Manager and Web Browser | |||||
OPTION | ||||||
-Intelligent Kits | DB9 port, dry contact | |||||
-USB | B-type USB port | |||||
-SNMP Kits | pluggable type | |||||
MECHANICAL | ||||||
-W╳D╳H (mm) | 438*426*86(2U) | 438*426*86(2U) | 438*476*173(4U) | 440*476*86(2U) | 438*476*173(4U) | 438*476*86(2U) |
(max) | 438*437*86 | 438*437*86 | 438*488*173 | 440*488*86 | 438*488*173 | 438*488*86 |
-W╳D╳H (mm)(shipment) | 580*565*250 | 580*565*250 | 580*660*335 | 580*615*250 | 580*660*335 | 580*615*250 |
-Net Weight (KG) | 13.5 | 8 | 28 | 9.5 | 33 | 10.5 |
-Package Weight(KG) | 16 | 11 | 31 | 12.5 | 36 | 13.5 |
-Rack / Tower | Rack and Tower | |||||
Color | Black default |
HR1106XS | HR1106XL | HR1110XS | HR1110XL | |
INPUT | ||||
Cold Start | YES Default output frequency will be 50Hz or settable |
|||
Acceptable Input Voltage | 110VAC~288VAC | |||
100% load@>176VAC | ||||
90% load@>154VAC | ||||
75% load@>132VAC | ||||
50% load@>110VAC | ||||
Phase | Single phase in,single phase out | |||
Transfer Voltage Range | 200VAC/208VAC/220VAC/230VAC/240VAC | |||
-Line low transfer | 110VAC | |||
-Line low recovery | 121VAC | |||
-Line high transfer | 288VAC | |||
-Line high recovery | 281VAC | |||
Input Current | ||||
-Rating(full charging) | 30A/220V | 34A/220V | 49A/220V | 53A/220V |
Input Power Factor | ≥0.99 | |||
Input current distortion | <4% | |||
Input Frequency Range | 40~70Hz | |||
OUTPUT | ||||
Frequency adaptable | Settable | |||
Power | ||||
-Power | 6KVA | 10KVA | ||
-Power(kW) | 6KW | 10KW | ||
Output Voltage | ||||
-Waveform(Bat. Mode) | Pure Sine Wave | |||
-Nominal voltage | 220VAC/230VAC/240VAC, 200VAC/208VAC(PF=0.9) | |||
-Voltage regulation | ± 1 % | |||
-Voltage distortion | ≤1% THD, linear load | |||
≤ 5% THD, non linear load | ||||
Output Frequency | ||||
-Synchronization range | ±5Hz default, settable | |||
-Battery mode | (50±0.1) Hz default | |||
Transfer Time | ||||
-Line mode to battery mode | 0ms | |||
-Inverter to bypass | 0ms | |||
Efficiency | ||||
-Line mode with battery full charged | 94.6%@100% load, 95%@60% load | |||
-ECO mode | 98.0% | |||
Noise(1m away) | <58dB | |||
Overload Capability(Inverter) | 105% to 110% : Transfer to bypass after 10 mins. | |||
111% to 125% : Transfer to bypass after 1 mins. | ||||
126% to 150%: Transfer to bypass after 30s | ||||
Overload Capability (Bypass Mode) | less than 125%: long time running | |||
126% to 130% :Shutdown in 5 mins | ||||
131% to 150% :Shutdown in 1 mins | ||||
> 150% :Shutdown in 200 ms | ||||
Crest Ratio | 3:1 | |||
BATTERY | ||||
Rating/Type | 12VDC/7Ah | Depend on the capacity of external batteries | 12VDC/9Ah | Depend on the capacity of external batteries |
Quantity | 16PCS | 16-20PCS settable | 16PCS | 16-20PCS settable |
DC Voltage | 192VDC default, settable | |||
Back-up Time | 3mins @5kW | Depend on the capacity of external batteries | 2mins @8kW | Depend on the capacity of external batteries |
Charger | ||||
-Charging current (max) | 1A, settable | 5A max,settable | 1A,settable | 5A max,settable |
-Float Charging Voltage | 2.25V/cell default, setttable via software | |||
-Boost Charging Voltage | 2.25V/cell default, setttable via software | |||
-Charging time | 8h recharge to 90% | Depend on the capacity of external batteries | 8h recharge to 90% | Depend on the capacity of external batteries |
Leakage current | <3mA | |||
Indicator & Alarm | ||||
-Display | LED+LCD | |||
Inteface | ||||
-Smart RS232 | Standard Cable support INVT Power Monitor Software | |||
-EPO | NC | |||
-RS485(option) | Installed in the intelligent slot | |||
-SNMP(option) | Power Managment from SNMP Manager and Web Browser | |||
Option | ||||
-Intelligent Kits | DB9 port, dry contact | |||
-parallel | 4 units paralleled | |||
-Super charger (12A) | digitally controlled, 4-steps charge, settable, @PF0.9 | |||
-USB | B-type USB port | |||
-SNMP Kits | Pluggable type | |||
Mechanical | ||||
-W╳D╳H (mm) | 440*660*172 | 440*550*86 | 440*660*172 | 440*550*86 |
-Net Weight (KG) | 58 | 16 | 62 | 18 |
-Package Weight (KG) | 63 | 18 | 68 | 21 |
-Rack / Tower | Rack/Tower | |||
Color | Black default |
View more about HR11 Series Rack Online UPS 1-10kVA (220V/230V/240V) on main site