HT31 Series Tower Online UPS 10-40kVA (220V/230V/240V)

HT31 Series Tower Online UPS 10-40kVA (220V/230V/240V)

Category: Single-Phase UPS

Specifications
Details

HT31 Series Tower Online UPS 10–40kVA (220V/230V/240V)

The HT31 Series 3:1 Tower Online UPS is a true double-conversion online UPS, powered by advanced DSP control technology. Designed for high performance and reliability, it offers a 12A optional charger, with a digital charger adjustable between 1A and 5A. This makes it an ideal solution for safeguarding computers, telecommunications equipment, and other sensitive electronics. Available in 10kVA, 15kVA, 20kVA, and 40kVA capacities.


Common Features

  • Comprehensive protection against overvoltage, short circuits, and overheating

  • Automatic fan speed control for efficient cooling

  • Rich connectivity options: RS232, USB, SNMP, Intelligent Card

  • Supports parallel operation of up to 4 units


Unique Features

  • Output Power Factor = 1 for maximum efficiency

  • Compact design with high power density

  • Digital charger adjustable from 1A to 5A

  • Optional 12A charger for large-capacity battery charging

Specifications

  HT3110XL HT3115XL HT3120XL   HT3140L
INPUT   INPUT  
Cold Start YES
Default output frequency will be 50Hz or settable
   
Acceptable Input Voltage L-L 190VAC~499VAC Acceptable Input Voltage L-L 190VAC~499VAC
  100% load@>305VAC   100% load@>305VAC
90% load@>266VAC 90% load@>266VAC
75% load@>228VAC 75% load@>228VAC
50% load@>190VAC 50% load@>190VAC
Phase Three phase in, single phase out Phase Three phase in,single phase out
Transfer Voltage Range    L-L 380/400/415VAC Transfer Voltage Range    L-L 380/400/415VAC
Line low transfer 190VAC Line low transfer 190VAC
Line low recovery 209VAC Line low recovery 209VAC
Line high transfer 499VAC Line high transfer 499VAC
Line high recovery 486VAC Line high recovery 486VAC
Input Current   Input Current  
Rating (nominal input voltage) 16.5A/380V 25A/380V 33A/380V Rating (nominal input voltage) 70A/380V
Input Power Factor 0.99 Input Power Factor 0.99
Input current distortion 4% Input current distortion 5%
Input Frequency Range 40~70Hz Input Frequency Range 40~70Hz
OUTPUT   OUTPUT  
Frequency adaptable Settable Frequency adaptable Settable
Power   Power  
Power 10KVA 15KVA 20KVA Power 40KVA
Power(kW)  10KW 15KW 20KW Power(kW)  36KW
Output Voltage   Output Voltage  
Waveform (Bat. Mode) Pure Sine Wave Nominal voltage L-N 220VAC/230VAC/240VAC,  200VAC/208VAC(PF=0.8)
Nominal voltage L-N 220VAC/230VAC/240VAC,  200VAC/208VAC(PF=0.9) Voltage regulation ± 1 %
Voltage regulation ± 1 % Voltage distortion 1% THD, linear load        
Voltage distortion 1% THD, linear load         3% THD, non linear load
3% THD, non linear load Output Frequency  
Output Frequency   Synchronization range ±5Hz default, ±1Hz,±2Hz,±3Hz,±4Hz,±5Hz settable
Synchronization range ±5Hz default, settable Battery mode (50±0.1) Hz
Battery mode (50±0.1) Hz default Bypass  
Transfer Time   Input mode Dual input (Alternative common input)
Line mode to battery mode 0ms Bypss voltage range upper limit:10%/15%/20%/25%@220VAC lower limit:10%/15%/20%@230VAC upper limit:10%/15%@240VAC lower limit:10%/20%/30%/40%
Inverter to bypass 0ms Bypss frequency range settable: ±1Hz,±2Hz,±3Hz,±4Hz,±5Hz; default: ±5Hz 
Efficiency   Bypass overload capacity less than 125%: long time running126% to 130% :Shutdown in 5 mins 131% to 150% :Shutdown in 1 mins > 150%  :Shutdown in 200 ms
Line mode with battery full charged 94%@100% load, 94.5%@70% load 94.2%@100% load, 95%@70% load 94.2%@100% load, 95%@50% load Transfer Time  
ECO mode 98.0% Line mode to battery mode 0ms
Noise (1m away)  <55dB <62dB <62dB Inverter to bypass 0ms
Overload Capability (Inverter) 105% to 110% : Transfer to bypass after 10 mins. Efficiency  
111% to 125% : Transfer to bypass after 1 mins. Line mode with battery full charged 94%@100% load, 94.5%@70% load
126% to 150%: Transfer to bypass after 30s ECO mode 98.0%
Overload Capability (Bypass Mode) less than 125%: long time running Overload Capability (Inverter) 105% to 110% : Transfer to bypass after 10 mins.
 126% to 130% :Shutdown in 5 mins 111% to 125% : Transfer to bypass after 1 mins.
 131% to 150% :Shutdown in 1 mins 126% to 150%: Transfer to bypass after 30s
> 150%  :Shutdown in 200 ms Noise (1m away) 65dB @ 100% load, 62dB @ 45% load
BATTERY   Crest Factor 3:1
Quantity 16-20PCS settable 16-20PCS settable 16-20PCS settable Battery  
DC Voltage 192VDC default, settable DC voltage ±240VDC
Charger   Charger Digital charger
Charging current (max) 5A max,settable 5A max,settable 5A max,settable     -Charging current (max) 20% *output power
Float Charging Voltage 2.25V/cell default, setttable via software Display LED + color touch LCD
Boost Charging Voltage 2.25V/cell default, setttable via software Interface Standard:RS232, RS485, USB,dry contact
Optional: SNMP,AS/400
Indicator & Alarm   Altitude <1000m, within 1000m to 2000m, power derate 1% for every 100m rise
Display LED+LCD Working Enviroment  
Inteface   storage  -40~70
Smart RS232 Standard Cable support INVT Power Monitor Software working 0~40, huminity 95% non condesation, attitude<1500m (@full load)
EPO NC, NO settable, forbidden default Mechanical  
RS485 (option) Installed in the intelligent slot WDH (mm) 600*980*950
SNMP (option) Power Managment from SNMP Manager and Web Browser Net Weight (KG) 170
Option   Color Black default
Intelligent Kits DB9 port, dry contact        
parallel 4 units paralleled        
Super charger (12A) digitally controlled, 4-steps charge, settable        
USB B-type USB port        
SNMP Kits Pluggable type        
Working Enviroment          
storage -40~70        
working 0~40, huminity 95% non condesation, attitude<3000m (@full load)        
Mechanical          
WDH (mm) 190*553*336 190*542*500        
Net Weight (kg) 18 26        
Package Weight (kg) 20 30        
Rack / Tower Tower        
Color Black default        