Details
HRC11 1-3kVA Rack Online UPS (220V/230V/240V)
The HRC11 1-3kVA Rack Online UPS is designed to convert alternating current (AC) mains power into a pure sine wave output, ensuring stable and clean electricity supply. In the event of a mains failure, the internal battery backup system takes over to maintain uninterrupted power to connected devices. This model is ideal for use in small server rooms and IT environments.
Key Features
-
High Output Power Factor
Enhanced load handling capability with excellent adaptability to various load types, including half-wave, inductive, and capacitive loads. -
Superior Input Performance
Achieves an input power factor of 0.99, with input harmonic current less than 3% and an overall system efficiency of up to 95.5%—delivering both energy savings and high operational efficiency. -
Advanced Battery Management
Features a fully digital control charger with intelligent 3-stage battery charging. Charging current is adjustable via the front panel, ranging from 1A to 12A. -
Event Recording & Analysis
Integrated event log system captures internal anomalies. Data can be exported to a PC and visualized as waveform diagrams for convenient troubleshooting and performance review. -
Versatile Communication Interfaces
Comes standard with RS232. Optional interfaces include USB, RS485, SNMP, EPO, AS400, BMS, battery temperature sensor, and network port surge protection—ensuring broad compatibility with various systems.
Specifications
HR1101CL | HR1101CS | HR1102CL | HR1102CS | HR1103CL | HR1103CS | |
Power | 1kVA/1kW | 2kVA/2kW | 3KVA | 3KVA | ||
Battery Cold Start | Standard | |||||
Input voltage range | 110VAC~300VAC | |||||
50% load@ 276VA~C300VAC;100% load@176VAC~276VAC;110VAC~176VAC load decrease linearly from 100%~50% | ||||||
Phase | Single Phase in, Single Phase out | |||||
Rated voltage | 220/230/240VAC | |||||
Line low transfer | 110VAC | |||||
Line low recovery | 120VAC | |||||
Line high transfer | 300VAC | |||||
Line high recovery | 290VAC | |||||
Input curent | ||||||
Rated Current | 4.9A | 9.7A | 14.5A | |||
Input Power Factor | ≥0.99 | |||||
THDi | <3% (100% Linear load); <5% (non-linear load) | |||||
Input frequency Range | 50/60±5Hz,±1Hz/±3Hz/±10Hz(Settable) | |||||
Output | ||||||
Frequency adaptable | Settable | |||||
Output Voltage | ||||||
Waveform(Bat. Mode) | Pure Sine Wave | |||||
Rated voltage | 220/230/240VAC, 200/208VAC(PF=0.9) | |||||
Voltage regulation | ± 1% | |||||
Dynamic response | ≤5% (0% - 100% -0%) | |||||
Dynamic recovery | ≤40ms (0% - 100% -0%) | |||||
Voltage distortion | <3% (100% Linear load); <5% (non-linear load) | |||||
Output Frequency | ||||||
Synchronization range | Mains mode: follow the mains frequency,Battery mode: 50/60Hz±0.1% | |||||
Transfer Time | ||||||
Line mode to battery mode | 0 | |||||
Inverter to bypass | 2ms | |||||
Effciency | ||||||
Line mode with fully charged battery | 94.5%@100% load | 95%@100% load | 95.5%@100% load | |||
ECO mode | 98.0% | 98.0% | 98.0% | |||
Battery mode | 89.5%@100% load | 91.5%@100% load | 91.5%@100% load | |||
Noise (1m away) | <43dB@<60%load, <47dB@>60%load | <50dB@<60%load, <55dB@>60%load | <50dB@<60%load, <55dB@>60%load | |||
Overload Capability (Inverter) | 102%~110%: Transfer to bypass after 30mins 110%~125%: Transfer to bypass after 10mins 125%~150%: Transfer to bypass after 30s |
|||||
Overload Capability (Battery Mode) | 102%~110%: Transfer to bypass after 1min 110%~125%: Transfer to bypass after 10s 125%~150%: Shutdown after 5s |
|||||
Overload Capability (Bypass Mode) | <130%: Long time operation 130%~150%: Shutdown after10mins 150%~180%: Shutdown after 5s |
|||||
Crest Factor | 3:1 | |||||
BATTERY | ||||||
Rating/Type | Depend on the capacity of external batteries | 12VDC/7Ah | Depend on the capacity of external batteries | 12VDC/7Ah | Depend on the capacity of external batteries | 12VDC/9Ah |
Quantity | 3 | 6 | 6 | |||
DC Voltage | 36VDC/48VDC (Support lithium battery) |
36VDC | 72VDC/96VDC (Support lithium battery) |
72VDC | 96VDC (Support lithium battery) |
72VDC |
Back-up Time | Depend on the capacity of external batteries | 3mins @80% load | Depend on the capacity of external batteries | 3mins @80% load | Depend on the capacity of external batteries | 3mins @80% load |
Battery Charger | ||||||
Charging Voltage | ||||||
Charging Current | 1-12A (Settable) | 1A | 1-12A (Settable) | 1A | 1-12A (Settable) | 1A |
Charging Time | Depend on the capacity of external batteries | 8h recharge to 90% | Depend on the capacity of external batteries | 8h recharge to 90% | Depend on the capacity of external batteries | 8h recharge to 90% |
INDICATOR & ALARM | ||||||
Display | LED+LCD | |||||
Battery Discharge | Sound once every 2 minutes | |||||
Low Battery Voltage | Sound once every 6s | |||||
Overload | Continuous beeping | |||||
Input Voltage Abnormal (Include Sequential Negative,Ground wire not connected) | Sound once every 2 minutes | |||||
Alarm | Sound once every 6s | |||||
Fault | Continuous beeping | |||||
INTERFACE | ||||||
RS232 | Support background software through standard cables | |||||
Input | IEC C14 | IEC C20 | ||||
Output | 4 National standard sockets | |||||
OPTION | ||||||
SNMP Card | Monitor the machine through the network | |||||
AS400 Dry Contact | Pluggable DB9 dry connector card or phoenix terminal | |||||
USB | B-type USB port | |||||
RS485 | RS485 communication interface | |||||
EPO | Emergency power off | |||||
External Battery Temperature | External battery temperature detection | |||||
RJ45 Surge Protection | Port Surge Protection | |||||
BMS | Dry contact for Lithium Battery BMS | |||||
MECHANICAL | ||||||
W*D*H(mm) | 440*377*86 | 440*427*86 | 440*427*86 | 440*577*86 | 440*427*86 | 440*577*86 |
W*D*H(mm) (Package size) |
580*515*250 | 580*565*250 | 580*565*250 | 580*717*250 | 580*565*250 | 580*717*250 |
Net weight (KG) | 5.5 | 12.8 | 7 | 21.9 | 7.3 | 24.9 |
Gross weight (KG) | 8.2 | 15.7 | 9.9 | 25.2 | 10.2 | 28.2 |
Color | Black | |||||
Batery Box (VRLA) Dimension | 440*426*86 |