The ‌HTD33 Series UPS‌ leverages a ‌double-conversion online design‌ and ‌DSP digital control‌ to deliver ‌pure sine wave output‌, ensuring zero downtime for computer systems, data centers, and telecom networks. By prioritizing ‌energy efficiency‌ (up to 96%) and ‌ultra-clean power‌ (PF >0.99, THDi <3%), it minimizes operational costs while protecting sensitive equipment from grid instability, harmonics, and surges.

Save Energy Bills & Carbon Footprint‌

96% efficiency with ECO-mode optimization.

‌Future-Proof Power Quality‌

PF >0.99 and THDi <3% with full-load capacity.

Lithium-Ready & Smart Maintenance‌

50%+ longer battery life vs. traditional solutions.

Space-Saving & Rapid Service‌

30% smaller footprint than competitors, with modular subsystems for <15-minute component swaps.

High Power Density and Easy Maintenance‌:

High power density design with full front maintenance and support for top and bottom cable entry methods, saving installation space.


Specifications

MODEL HTD33120 HTD33160 HTD33200
System Capacity 120kVA 160kVA 200kVA
Power Module Capacity 60kVA/60kW 80kVA/80kW 100kVA/100kW
Main Input      
Grid System 3P+N+PE
Rated Input Voltage 380/400/415VAC (line-line)
Rated Frequency 50/60Hz
Input Voltage Range 323~478Vac (line-line), full load @ 30~40℃
323~138Vac (line-line), load decrease linearly from 100% load to 30% load @ 30~40℃
Input Frequency Range 40Hz~70Hz
Input Power Factor >0.99
Input Current THDi <3% (full Linear load)
Bypass  
Rated Bypass Voltage 380/400/415VAC (line-line)
Rated Bypass Frequency 50/60Hz
Bypass Voltage Range Settable, default -20%~+15%
Upper limited: +10%, +15%, +20%, +25%
Lower limited: -10%,  -15%, -20%, -30%,  -40%
Bypass Frequency Range Settable, ±1Hz, ±3Hz, ±5Hz
Bypass Overload 125%, long term operation
125%~130%, 10 minutes
130%~150%, 1 minute
>150%, 300ms
Output  
Rated Voltage 380/400/415VAC (line-line)
Rated Frequency 50/60Hz
Output Power Factor 1
Voltage Precision ±1%
Transient Response <5%   (0% - 100% -0% step load)
Transient Recovery < 40ms (0% - 100% -0% step load)
Output Voltage THDu <1%, linear load
<5%, non-linear load (IEC/EN62040-3)
Inverter Overload <110%, 60 mins
110%~125%, 10mins
125%~150%, 1min
>150%, 200ms
Frequency Regulation 50/60Hz±0.1%
Synchronized Range Settable, ±0.5Hz~±5Hz, default ±3Hz
Synchronized Slew Rate Settable, 0.5Hz/S~3Hz/S, default 0.5Hz/S
Battery and Charger  
Battery Rated Voltage ±240VDC
30pcs derated 0.7
32~34pcs derated 0.8
36~38pcs derated 0.9
40~48pcs non-derating
Charger Voltage Precision 1%
Charger Power max=15% * Output active power
Effiency  
Normal Operation >96%
Battery Operation >95%
Power Module Weight (kg) 44.8 51.2 53.5
System  
Display LCD + LED + Color touch screen
Interface RS485, USB, CAN, Programmable dry contact, 2 intelligent card slots, 1 expandable dry contact slot
Option
SNMP card, AS400, Parallel kit, Lightning protection components, Copper bar, LBS, SMS alarm, RS485 expansion card
Environment  
Operation Temperature 0~40 ℃
Storage Temperature -40~70 ℃
Relative Humidity 0 ~ 95% Non condensing
Noise (1 meter) 75dB @ 100% load, 70dB @ 45% load
Altitude <1000m, Load derated 1% per 100m From 1000~2000m
Physical  
Cabinet Dimension
(W*D*H, mm)
480*1100*1200
Cabinet Weight (kg) 78.8
Power Module Dimension
(W*D*H, mm)
440*795*174
Power Module Weight (kg) 44.8 51.2 53.5