HT33 Series Tower Online UPS 120kVA-200kVA (380V/400V/415V)
Category: Three-Phase UPS
Specifications
Details
HT33 Series Tower Online UPS 120kVA-200kVA (380V/400V/415V)
The HTD33 Series UPS leverages a double-conversion online design and DSP digital control to deliver pure sine wave output, ensuring zero downtime for computer systems, data centers, and telecom networks. By prioritizing energy efficiency (up to 96%) and ultra-clean power (PF >0.99, THDi <3%), it minimizes operational costs while protecting sensitive equipment from grid instability, harmonics, and surges.Save Energy Bills & Carbon Footprint
96% efficiency with ECO-mode optimization.
Future-Proof Power Quality
PF >0.99 and THDi <3% with full-load capacity.
Lithium-Ready & Smart Maintenance
50%+ longer battery life vs. traditional solutions.
Space-Saving & Rapid Service
30% smaller footprint than competitors, with modular subsystems for <15-minute component swaps.
High Power Density and Easy Maintenance:
High power density design with full front maintenance and support for top and bottom cable entry methods, saving installation space.
Specifications
MODEL | HTD33120 | HTD33160 | HTD33200 |
System Capacity | 120kVA | 160kVA | 200kVA |
Power Module Capacity | 60kVA/60kW | 80kVA/80kW | 100kVA/100kW |
Main Input | |||
Grid System | 3P+N+PE | ||
Rated Input Voltage | 380/400/415VAC (line-line) | ||
Rated Frequency | 50/60Hz | ||
Input Voltage Range | 323~478Vac (line-line), full load @ 30~40℃ 323~138Vac (line-line), load decrease linearly from 100% load to 30% load @ 30~40℃ |
||
Input Frequency Range | 40Hz~70Hz | ||
Input Power Factor | >0.99 | ||
Input Current THDi | <3% (full Linear load) | ||
Bypass | |||
Rated Bypass Voltage | 380/400/415VAC (line-line) | ||
Rated Bypass Frequency | 50/60Hz | ||
Bypass Voltage Range | Settable, default -20%~+15% Upper limited: +10%, +15%, +20%, +25% Lower limited: -10%, -15%, -20%, -30%, -40% |
||
Bypass Frequency Range | Settable, ±1Hz, ±3Hz, ±5Hz | ||
Bypass Overload | 125%, long term operation 125%~130%, 10 minutes 130%~150%, 1 minute >150%, 300ms |
||
Output | |||
Rated Voltage | 380/400/415VAC (line-line) | ||
Rated Frequency | 50/60Hz | ||
Output Power Factor | 1 | ||
Voltage Precision | ±1% | ||
Transient Response | <5% (0% - 100% -0% step load) | ||
Transient Recovery | < 40ms (0% - 100% -0% step load) | ||
Output Voltage THDu | <1%, linear load <5%, non-linear load (IEC/EN62040-3) |
||
Inverter Overload | <110%, 60 mins 110%~125%, 10mins 125%~150%, 1min >150%, 200ms |
||
Frequency Regulation | 50/60Hz±0.1% | ||
Synchronized Range | Settable, ±0.5Hz~±5Hz, default ±3Hz | ||
Synchronized Slew Rate | Settable, 0.5Hz/S~3Hz/S, default 0.5Hz/S | ||
Battery and Charger | |||
Battery Rated Voltage | ±240VDC 30pcs derated 0.7 32~34pcs derated 0.8 36~38pcs derated 0.9 40~48pcs non-derating |
||
Charger Voltage Precision | 1% | ||
Charger Power | max=15% * Output active power | ||
Effiency | |||
Normal Operation | >96% | ||
Battery Operation | >95% | ||
Power Module Weight (kg) | 44.8 | 51.2 | 53.5 |
System | |||
Display | LCD + LED + Color touch screen | ||
Interface | RS485, USB, CAN, Programmable dry contact, 2 intelligent card slots, 1 expandable dry contact slot | ||
Option | SNMP card, AS400, Parallel kit, Lightning protection components, Copper bar, LBS, SMS alarm, RS485 expansion card |
||
Environment | |||
Operation Temperature | 0~40 ℃ | ||
Storage Temperature | -40~70 ℃ | ||
Relative Humidity | 0 ~ 95% Non condensing | ||
Noise (1 meter) | 75dB @ 100% load, 70dB @ 45% load | ||
Altitude | <1000m, Load derated 1% per 100m From 1000~2000m | ||
Physical | |||
Cabinet Dimension (W*D*H, mm) |
480*1100*1200 | ||
Cabinet Weight (kg) | 78.8 | ||
Power Module Dimension (W*D*H, mm) |
440*795*174 | ||
Power Module Weight (kg) | 44.8 | 51.2 | 53.5 |
View more about HT33 Series Tower Online UPS 120kVA-200kVA (380V/400V/415V) on main site