RM Series Rack-Mounted Modular Online UPS 5-20kVA (380V/400V/415V)

RM Series Rack-Mounted Modular Online UPS 5-20kVA (380V/400V/415V)

Category: Modular Online UPS

Specifications
Details

RM Series Rack-Mounted Modular Online UPS 5–20kVA (380V/400V/415V)

The RM Series is a single-phase rack-mounted modular UPS system, capable of housing up to 6 power modules (maximum 20kVA), 5 battery module groups, and an optional 10A charging module. It offers flexible configurations including 1-phase input and output without derating—making it ideal for diverse project requirements. Fully compatible with standard 19” server cabinets, the RM Series delivers a complete tower-style modular UPS solution, perfect for small to medium-sized server rooms.


Key Features

  1. Modular 3:1 or 1:1 UPS Configuration
    Adaptable input/output phase options to suit varying system needs.

  2. Three-Phase PFC Rectifier
    Ensures high input power factor and reduced harmonic distortion.

  3. Hot-Swappable Battery Packs
    Easy battery maintenance without system downtime.

  4. Compatible with LFP Batteries
    Supports lithium iron phosphate batteries for enhanced safety and lifespan.

  5. Optional 10A Charging Module
    Provides faster battery charging to ensure system readiness.

  6. Battery Module Temperature Monitoring
    Real-time temperature detection for optimized battery performance and protection.

Specifications

Module RM3120/05D
System Capacity 20kVA
Input Phase 3Phase+Neutral+Ground, 380V/400V/415V (line to line)
220V/230V /240V (line to neutral)
Input Voltage Range 277~478Vac (line-line),full load, 147~277Vac (line-line), load decreases linearly from 100%~50%
Rate Frequency 50/60Hz
Inout Frequency Range 40~70Hz
Input PF >0.99
Input THDi <5% (100%Linear load)
Bypass Rate Voltage 380V/400V/415V, line to line
Rate Frequency 50/60Hz
Input  Voltage Range settable,  default -20%~+15%
upper limit: +25%; lower limit: -40%
Bypass Frequency Range settable,±1Hz, ±3Hz, ±5Hz
Bypass Overload Capabiltiy 125%, long time operation, 125%< load <130%, last for 5 minutes, 130%<load<150%, last for 1 minute, >150%, last for 200ms
Output Rate Voltage 220V/230V/240V, line to neutral
Voltage Precision ±2%
Rate Frequency 50/60Hz±0.01%
Output PF 1
Output THDu <1% linear load, <5% non-linear load (IEC/EN62040-3)
Inverter Overload Normal <110% for 1 hour; 110%~130% for 10 minutes; 130%~150% for 1 minutes; >150% for 200ms
Battery <110% for 10 minutes; 110%~125% for 1 minute; 125%~130% for 10s; >130% for 200ms
Synchronization Range settable,±0.5Hz/s~±5Hz/s, default ±3Hz/s
Synchronization Rate settable,0.5Hz/s~3Hz/s, default 0.5Hz/s
Output Dynamic Response <5% (20%-80%-20% step load)
Dynamic Recovery Time <20ms (0%-100%-0% step load)
Battery Voltage 144VDC(12pcs)
Charge Power 0~1.8A settable(each module)
Charger Voltage Precision 1%
System Efficiency AC Mode: >94.5%; ECO Mode: >98%; Battery Mode: >90%
Display LCD+LED, 7" touch color screen and keyboard
IP Class IP20
Interface Standard: RS232,RS485,USB, Dry contacts
Option SNMP card,AS400 card, parallel kits, SPD, dust filter,LBS
Temperature Operation: 0-40℃  Storge: -40~70℃
Relative Humidity 0-95% Non-comdensing
Altitude <1000m, Load derated 1% per 100m From 1000~2000m
Noise(dB) 55dB @100% load
Applicable Standard Safety: IEC/EN 62040-1 EMC: IEC/EN 62040-2 PERFORMANCE: IEC/EN 62040-3
Physical         RM3120 Battery
Weight(kg) Cabinet: 66.5kg 67.3kg
Module: 7.5kg 17.8kg
Dimension(W*D*H)(mm) Cabinet 443*695*928
Module 200*431*84.5 200*516*84.5

View more about RM Series Rack-Mounted Modular Online UPS 5-20kVA (380V/400V/415V) on main site